Cool homes in summer:the thermal time lag.
In winter what matters is how much heat leaves the house; in summer, when and how much heat gets in. The time lag measures exactly that: how many hours the afternoon heat takes to cross walls and roof. Here you find what it means, how to read it and the values of the most common timber build-ups.

Three numbers to understand summer comfort
01
Time lag
The delay, in hours, between the temperature peak outside and the peak reaching the inside surface. If the sun heats the wall at 3 pm and the time lag is 12 hours, the heat gets inside around 3 am, when it is already cool outside and opening the windows is enough.
02
Decrement factor
How much the heat wave shrinks while crossing the build-up. A factor of 0.10 means only 10% of the outside swing reaches the inside: an 11 °C swing outside becomes about 1 °C inside.
03
Periodic transmittance YIE
It combines both effects in a single value (W/m²K) and is the one required by Italian law: below 0.10 for walls (or mass over 230 kg/m²), below 0.18 for roofs. The lower it is, the cooler the house stays.
Watch a summer day inside the house
The example uses an X-LAM wall with wood-fibre external insulation. The afternoon heat takes many hours to cross the wall and reaches the inside at night, much weaker: that is the moment to open the low and high windows, so cool air comes in and warm air leaves from the top (stack effect).
Afternoon: the sun heats the wall the most, peak at 15:00. Inside, the house stays cool.
Illustrative animation: outside sol-air wave peaking at 40 °C at 15:00, time lag and decrement of your build-up, night ventilation from 21:00 to 7:00 when it is cooler outside than inside.
Summer performance classes
The Italian national guidelines for energy certification classify the envelope by time lag and decrement factor.
| Class | Time lag | Decrement | Performance |
|---|---|---|---|
| I | over 12 h | below 0.15 | Excellent |
| II | 10 – 12 h | 0.15 – 0.30 | Good |
| III | 8 – 10 h | 0.30 – 0.40 | Average |
| IV | 6 – 8 h | 0.40 – 0.60 | Sufficient |
| V | below 6 h | over 0.60 | Poor |
Time lag of timber walls and roofs
Values calculated live with our calculator for the ready-made models (zone E, inside 20 °C). Change materials and thicknesses in the calculator below to get the values of your project.
| Build-up | Thickness | U W/m²K | Time lag | Decrement | Class |
|---|---|---|---|---|---|
| Timber-frame wall with wood-fibre ETICS | 256 mm | 0,200 | 10,6 h | 0,37 | III |
| Ventilated timber-frame wall with timber cladding | 278 mm | 0,159 | 10,5 h | 0,32 | III |
| X-LAM wall with graphite EPS ETICS | 259 mm | 0,181 | 7,6 h | 0,37 | IV |
| X-LAM wall with wood-fibre ETICS | 331 mm | 0,164 | 16,3 h | 0,07 | I |
| Ventilated rafter roof with wood fibre | 280 mm | 0,160 | 10,9 h | 0,31 | III |
| Ventilated X-LAM roof with rock wool | 340 mm | 0,141 | 14,7 h | 0,15 | II |
| Ventilated X-LAM roof with PIR | 260 mm | 0,134 | 9,3 h | 0,30 | III |
What keeps a timber house cool
- 01
Insulation with high heat capacity
Wood fibre stores about 2,100 J/kgK against 1,000–1,450 for mineral wools and polystyrenes: with the same thickness and a higher density it slows the heat wave much more.
- 02
Mass where it is needed
An X-LAM panel combined with wood-fibre external insulation adds mass and heat capacity: it is the combination that most easily takes the time lag beyond 12 hours.
- 03
Ventilated roof and façade
The ventilated gap under the tiles or behind the timber cladding removes much of the sun's heat before it reaches the insulation.
- 04
Light colours and shading
A light roof covering and sunshades or shutters reduce the temperature the sun brings to the surfaces: the wave to be delayed starts lower.
- 05
Night ventilation
The time lag works if the heat is let out at night: open windows or mechanical ventilation in the cool hours complete the work of the envelope.
Calculate the time lag and U-value of your build-up
Pick a timber-frame or X-LAM wall or roof, change materials and thicknesses: you instantly see time lag, decrement, U-value, legal check and condensation risk. You can compare up to three build-ups and download the PDF.
Indicative estimate, it does not replace the calculation of a qualified engineer. Transmittance to EN ISO 6946 (Rsi 0.13 walls / 0.10 roofs, Rse 0.04; layers with studs: mean of upper and lower limits; beyond a strongly ventilated air gap Rse = Rsi). Time lag, decrement and YIE to EN ISO 13786 over a 24-hour period. Condensation: steady-state Glaser method in the design conditions entered (EN ISO 13788), without monthly balance. U limits: Italian DM 26/06/2015, values from 2021. Material properties: typical values, to be replaced with those declared by the manufacturer.
FAQ
Frequently asked questions about the time lag
Why trust us
Figures, certifications and public works that speak for us.
- 1905
- Year founded
- 944
- Structures built
- 9.000 m³
- Timber processed every year
- CE0407-CPR-1459
- ISO 9001n. 3919760
- PEFCCSQA-PEFC-COC-54966
- STCAttestato 22/22-CL
Let's buildsomething that lasts.
Head office
Company details